Link To Ralspeed Home PageLink To Ralspeed Profile PageLink To Ralspeed Products PageLink To Ralspeed Applications PageLink To Ralspeed Questions & Answers PageLink To Ralspeed Case Studies PageLink To Ralspeed Latest News PageLink To Ralspeed Keypad Demonstration PageLink To Ralspeed Downloads PageLink To Ralspeed Enquiries Page
Ralspeed Motor Control System

Questions & Answers

Q6 THE MOTOR DOES NOT ACCELERATE PROPERLY

Down Arrow Start- current control
 
Has the correct value of Current limit been set?

No
Right Arrow

In order for a motor to accelerate successfully on soft start control it will need to draw at least 200 to 350% of FLC, depending on the load. Ensure that the current limit is not set too low.
Down Arrow Start- voltage control
 
Has the pedestal and ramp times been set correctly?

Yes
Right Arrow

If the ramp-up is set to VOLTAGE then the user must input the correct values in order to achieve a smooth acceleration to full speed. Pedestal should be 35-40% ramp-up 10-30secs, target 90 to 100%. Other values are possible but may lead to problems.
Down Arrow Yes
   
Is the motor overloaded?

Yes
Right Arrow

If the motor is overloaded the soft starter will attempt to overcome the load problems but the motor may not allow the acceleration to proceed smoothly.
Down ArrowNo
   
Is the power supply weak?
Yes
Right Arrow
If the mains power supply is poor the acceleration current may cause the voltage to 'dip' and consequently the soft starter will lose control of the ramp-up.
Down ArrowNo
   
CONTACT YOUR SUPPLIER