Link To Ralspeed Home PageLink To Ralspeed Profile PageLink To Ralspeed Products PageLink To Ralspeed Applications PageLink To Ralspeed Questions & Answers PageLink To Ralspeed Case Studies PageLink To Ralspeed Latest News PageLink To Ralspeed Keypad Demonstration PageLink To Ralspeed Downloads PageLink To Ralspeed Enquiries Page
Ralspeed Motor Control System

Controlling Slip-Ring Motors

WITH THE TORQ-MASTER SOFT STARTER

The Torq-Master soft starter is an electronic method of starting ( and stopping ) three phase squirrel cage motors, wound rotor or slip-ring motors.

With slip-ring motors, 'shorting-out' the slip-rings makes starting difficult as these motors have little or no starting torque. To achieve a satisfactory start, Ralspeed fit the Torq-master with a torque increasing resistor for connecting to the rotor terminals, which, when the motor is operating at full speed, is then automatically 'shorted-out,' this resistance being approximately 10% of conventional resistance sizes.

Slip Ring Motor Applications

Ralspeed have supplied these starters for Rock Crushers, Rolling Mills, Sewage Pumps etc. Additional advantages of the Torq-Master soft starter, included as standard are :

  1. Electronic Overload.
  2. Three Control Options - Keypad, Terminals & Serial Port.
  3. Three methods of starting and ( if required ) stopping.
  4. LCD Display makes monitoring current, status and fault diagnosis easy, as the messages appear in English on the display.
  5. A by-pass contactor is fitted enabling the thyristors to 'shut-down' once up to speed, thus dramatically reducing heat-loss. With this feature the unit can be enclosed in an IP65 Enclosure.

Option 1 - Chassis Version 1 - CHASSIS VERSION

Sheet steel backplate complete with :-
  •  By-pass Contactor
  •  Resistance Shorting Contactor
  •  Torque Increasing Resistor (supplied loose)

Option2 - Enclosed Version
( to customer spec. ) Typical Example

Sheet Steel Enclosure, wall mounting ( up to 110kw ), floor standing ( 110kw upwards ), cable entry bottom / top ( to be specified ), finished to company colour, complete with :-
  •  Door Interlocked Isolator
  •  By-pass Contactor
  •  Resistance Shorting Contactor
  •  Torque increasing Resistor
  •  Start / Stop / Reset Pushbuttons
  •  Run Lamp
  •  Viewing Window for LCD Display

 

STANDARD FEATURES OF TORQ-MASTER

  •  Electronic Overload
  •  'Shear Pin' Protection
  •  Triple ramp-up
  •  Triple ramp-down
  •  Thermistor Input & Trip Facility
  •  RS485 Serial Link
  •  Torque Boost ( Kick Start )
  •  Comprehensive fault monitoring
  •  LCD Alphanumeric Display
  •  Current Limit
  •  Under Load Trip
  •  Relay Outputs - Ready, Run, Trip and Top of Ramp
  •  CE Marked
  •  Millennium Compliant ( no 'real time' chip is used )

 

Slip Ring Motor Starter
ITEM OPTION CODE KW FLC HxWxD - MM
1 1 TQM2k-SR-37 37 66 950 x 750 x 275
2 1 TQM2k-SR-55 55 100 950 x 750 x 264
3 1 TQM2k-SR-75 75 135 1150 x 750 x 275
4 1 TQM2k-SR-110 110 200 1150 x 750 x 275
5 1 TQM2k-SR-132 132 240 1550 x 750 x 350
6 1 TQM2k-SR-160 160 280 1550 x 750 x 350
7 1 TQM2k-SR-200 200 340 1550 x 1150 x 350
8 1 TQM2k-SR-250 250 445 1550 x 1150 x 350
           
9 2 TQMC2k-SR-37 37 66 1000 x 800 x 300
10 2 TQMC2k-SR-55 55 100 1000 x 800 x 300
11 2 TQMC2k-SR-75 75 135 1200 x 800 x 300
12 2 TQMC2k-SR-110 110 200 1200 x 800 x 300
13 2 TQMC2k-SR-132 132 240 1700 x 800 x 400
14 2 TQMC2k-SR-160 160 280 1700 x 800 x 400
15 2 TQMC2k-SR-200 200 340 1700 x 1200 x 400
16 2 TQMC2k-SR-250 250 445 1700 x 1200 x 400

DIMENSIONS NOT FOR MANUFACTURING PURPOSES AND DO NOT SHOW RESISTOR SIZES

All products are CE marked and are millennium compliant as no 'real time clock' is used

 

Top of page

 PHONE : 01254 582345 Web Design by eBusiness UK Ltd