Questions & Answers
Q2 THE SOFT STARTER DOES NOT RUN
|
The user must select terminals in the options menu in order that stop/start signals generated external to the soft starter can operate the unit. | |
|
As explained in section 7.5 of the manual there are various programmable inputs so that the user can configure his control system. If, for example, program 1 has been set for local/remote and the input is set high it will have moved the control function from the terminals (remote) to the keypad (local). Therefore, the user will have to remove this input before the terminals will be active | |
| |
||
|
The stop/start control is either through push buttons, relay or switch contact. If buttons are used the START button must be connected to terminals 1 & 2. The STOP button must be connected to terminals 1 & 3. If a relay or switch contact is used the user must link 1 & 2 and switch between 1 & 3 to give start and stop functions. | |
| CONTACT